Numerical study on effects of door-opening on airflow patterns and dynamic cross-contamination in an ISO class 5 operating room

Shuyun Dong , Guangbei Tu , Rongguang Cao , Zhenfeng Yu

Transactions of Tianjin University ›› 2009, Vol. 15 ›› Issue (3) : 210 -215.

PDF
Transactions of Tianjin University ›› 2009, Vol. 15 ›› Issue (3) : 210 -215. DOI: 10.1007/s12209-009-0037-y
Article

Numerical study on effects of door-opening on airflow patterns and dynamic cross-contamination in an ISO class 5 operating room

Author information +
History +
PDF

Abstract

The contamination diffusion to the operating room when the door is open was simulated with a computational fluid dynamic(CFD) method, to give the extent of the contamination diffusion. The influence of the door-opening procedure was ignored since the door of the operating room is normally a sliding one. The flow field in the case of the 16 s course of opening the door was simulated. The simulated and the experimental results demonstrate that the extent of the contamination diffusion is around 1.5 m when there is no temperature difference between indoor and outdoor, and there is hardly any contamination diffusion when the temperature difference is 1 °C. It can be concluded that the positive pressure difference in the operating room lost its function in preventing the contamination when the door is open. That the temperature of corridor is lower than that of operating room contributes to contamination control. Keeping 1 °C temperature difference between corridor and operating room and increasing positive pressure and air flow are suggested. It is more secure to set up an anteroom if persons come in or out of the operation room at the course of surgery.

Keywords

contamination control / computational fluid dynamic method / operating room / door-opening / biological clean operating room

Cite this article

Download citation ▾
Shuyun Dong, Guangbei Tu, Rongguang Cao, Zhenfeng Yu. Numerical study on effects of door-opening on airflow patterns and dynamic cross-contamination in an ISO class 5 operating room. Transactions of Tianjin University, 2009, 15(3): 210-215 DOI:10.1007/s12209-009-0037-y

登录浏览全文

4963

注册一个新账户 忘记密码

References

[1]

Schicht H H. 40 years of cleanroom technology—Some historical remarks [C]. In: Proceedings of the 17th International Symposium on Contamination Control. Bonn, Germany, 2004. 1–10.

[2]

Woloszyn M., Virgone J., Melen Stephane. Diagonal air-distribution system for operating rooms: Experiment and modeling[J]. Building and Environment, 2004, 39(10): 1171-1178.

[3]

Chow T.-T., Yang X.-Yu. Performance of ventilation system in a non-standard operating room[J]. Building and Environment, 2003, 38(12): 1401-1411.

[4]

Zhang Rui, Tu Guangbei, Ling Jihong. Study on biological contaminant control strategies under different ventilation models in hospital operating room [J]. Building and Environment (accepted).

[5]

Chow T-T, Ward S, Liu J P et al. Airflow in hospital operating theatre: The Hong Kong experience [C]. In: Proceedings of the 6th International Conference on Healthy Buildings. Espoo, Finland, 2000. 419–424.

[6]

Fletcher C. A. J., Mayer I. F., Eghlimi A., et al. CFD as a building services engineering tool[J]. International Journal on Architectural Science, 2001, 2(3): 67-82.

[7]

Yan Delong. Selection for and discussion on pressure differential control methods for cleanrooms [J]. Contamination Control and Airconditioning Technology, 2005(4): 12–14, 20(in Chinese).

[8]

Shen Jinming. Concept and feature of China code for clean operating room [J]. Contamination Control and Airconditioning Technology, 2006(S1): 1–6(in Chinese).

[9]

Wisemen Brian. Room pressure for critical environments[J]. ASHRAE Journal, 2003, 45(2): 34-39.

[10]

Gill K. E. HVAC design for isolation rooms[J]. Heating, Piping and Air Conditioning, 1994, 66(2): 45-52.

[11]

Dong S., Tu G., Ji Y., et al. Effects of door opening on cleanliness in operating room[J]. Journal of Tianjin University, 2007, 40(4): 489-493.

[12]

Dong S., Yu Z., Tu G., et al. Effects of a clean air supply unit combined to the center air conditioning system for the operating room on the local clean class[J]. Journal of Tianjin University, 2006, 39(10): 1227-1231.

[13]

Chen H., Tu G. B., Francis W. H. Yik. Simulation of variable air volume system with different duct layout[J]. Transactions of Tianjin University, 2004, 10(1): 24-28.

[14]

Na Y., Xing J., Tu G., et al. Numerical analysis of influencing factors on temperature field and airflow distribution of the displacement ventilation system[J]. Transactions of Tianjin University, 2005, 11(1): 66-72.

[15]

Tao Wenquan. Numerical Heat Transfer[M]. 2001 2nd Ed. Xi’an: Xi’an Jiaotong University Press.

AI Summary AI Mindmap
PDF

128

Accesses

0

Citation

Detail

Sections
Recommended

AI思维导图

/