As indicated in Fig.1, it is important for GFMs to realize inrush current limitation at stage I and maintain transient stability at stage II. When the fault is cleared, GFMs need to re-synchronize with the grid as soon as possible at stage III. This is because both inrush current and transient instability issues will lead to the failure of FRT process and result in tripping of the GFMs. To date, the transient response of the GFMs throughout the FRT process has not been thoroughly discussed. In existing studies, different FRT control strategies have been proposed [
11–
20], such as mode-switching control (MSC) [
11–
12], virtual impedance control (VIC) [
13–
16], and internal current limiter control (CLC) [
17–
18]. A current-restraining method based on MSC was proposed in Ref. [
11], which involves varying the GFMs from voltage control mode to current control mode to regulate output current directly during grid fault periods. When the fault is cleared, the GFMs need to recover to the normal control mode and realize re-synchronization with the grid again, which is accomplished by introducing the concept of virtual line impedance. However, the re-synchronization capability of GFMs is sensitive to controller parameters, and the effect of virtual line impedance has not been revealed, which probably result in the continuous-oscillation phenomenon. In Ref. [
14], virtual impedance is added to GFMs to limit fault current when grounded faults are detected. However, the inrush current elimination performance of VIC is limited in first several cycles due to the existence of an aperiodic fault current component [
1]. Another method was proposed in Ref. [
15], which shows that the GFMs can achieve fault current control via additional virtual admittance and adjustable virtual impedance [
16]. However, it is questionable whether the transient response of this method is quick enough to deal with inrush current issues. Furthermore, inrush current limiting can be achieved by using inherent current limiters in voltage and current multiple control loops, since the reference current can be simply restrained by limiters [
17]. However, the windup and latch-up introduced by limiters would reduce the stable operation domain and brings difficulties in the re-synchronization process [
18]. Moreover, the output active power and reactive power of GFMs with CLC would be uncontrollable during the transient period.