Performance analysis of solar absorption-subcooled compression hybrid refrigeration system in subtropical city

  • Xiangyang YE ,
  • Liming LIU ,
  • Zeyu LI
Expand
  • School of Electric power, South China University of Technology, Guangzhou 510640; Key Laboratory of Efficient and Clean Energy Utilization of Guangdong Higher Education Institutes, Guangzhou 510641, China

Received date: 06 May 2016

Accepted date: 04 Jul 2016

Published date: 20 Mar 2019

Copyright

2017 Higher Education Press and Springer-Verlag Berlin Heidelberg

Abstract

Solar absorption-subcooled compression hybrid refrigeration system is a new type of efficient and economical solar refrigeration device which always meets the demand of cooling load with the change of solar irradiance. The performance of the hybrid system is higher due to the improvement of evaporator temperature of absorption subsystem. But simultaneously, the variation of working process as well as performance is complicated since the absorption and compression subsystems are coupled strongly. Based on the measured meteorological data of Guangzhou, a subtropical city in south China, a corresponding parametric model has been developed for the hybrid refrigeration system, and a program written by Fortran has been used to analyze the performance of the hybrid system under different external conditions. As the condensation temperature ranges from 38°C to 50°C, the working time fraction of the absorption subsystem increases from 75% to 85%. Besides, the energy saving fraction also increases from 5.31% to 6.02%. The average COP of the absorption subsystem is improved from 0.366 to 0.407. However, when the temperature of the absorption increases from 36°C to 48°C, the average COP of hybrid system decreases from 2.703 to 2.312. Moreover, the working time fraction of the absorption subsystem decreases from 80% to 71.7%. The energy saving fraction falls from 5.67% to 5.08%. In addition, when the evaporate temperature increases from 4°C to 14°C, the average COP of the absorption subsystem decreases from 0.384 to 0.365. The work of the compressor decreases from 48.2 kW to 32.8 kW and the corresponding average COP of the absorption subsystem is improved from 2.591 to 3.082.

Cite this article

Xiangyang YE , Liming LIU , Zeyu LI . Performance analysis of solar absorption-subcooled compression hybrid refrigeration system in subtropical city[J]. Frontiers in Energy, 2019 , 13(1) : 185 -192 . DOI: 10.1007/s11708-017-0452-z

Acknowledgements

This work is supported by the National Science Foundation of China (Grant No. 51206056), the Fundamental Research Funds for the Central Universities (No. 2014ZZ0016) and the Key Laboratory of Efficient and Clean Energy Utilization of Guangdong Higher Education Institutes (No. KLB10004).
1
Tang P W, Chen G M, Tang L M. Simulation of a new combined absorption-compression refrigeration cycle. Cryogenics, 2011, 32(4): 21–26 (in Chinese)

2
He L J, Zhao J M, Chen G M, Tang L M, Wu Y F. Experimental comparison study on performances of new absorption-compression refrigeration system. Renewable Energy Resources, 2014, (2): 207–210 (in Chinese)

3
Cao Y R, Zhang X S, Bao H L. Analysis of new compressed and absorbered compound cycle driven by solar energy. Fluid Machinery, 2002, 30(10): 51–53 (in Chinese)

4
Zhao Z C, Zhang X D. Thermal performance analysis of ammonia absorption-compression refrigeration cycle driven by low temperature waste heat. Chemical Industy and Engineering Progress, 2009, (S1): 459–462 (in Chinese)

5
Zhou Y, Xie J L, Shen G M. The optimum performance analysis of a solar-assisted combined absorptionvapor compression air-conditioning system. Building Energy & Environment, 2002, (4): 1–3 (in Chinese)

6
Herold K E, Howe L A, Radermacher R. Analysis of a hybrid compression-absorption cycle using lithium bromide and water as the working fluid. International Journal of Refrigeration, 1991, 14(5): 264–272

DOI

7
Fukuta M, Yanagisawa T, Iwata H, Tada K. Performance of compression-absorption hybrid refrigeration cycle with propane/mineral oil combination. International Journal of Refrigeration, 2002, 25(7): 907–915

DOI

8
Tarique S M, Siddiqui M A. Performance and economic study of the combined absorption-compression heat pump. Energy Conversion and Management, 1999, 40(6): 575–591

DOI

9
Li Z Y, Liu J P. Performance test of compound parabolic concentrator and economic analysis of high temperature solar refrigeration system applied in subtropical city. Proceedings of the 2013 International Conference on Energy, Hengshan, China, 2013, 39–44

Outlines

/