School of Electrical and Information Engineering, Tianjin University, Tianjin 300072, China
shiweishuo@tju.edu.cn (Weishou SHI)
jinwei.he@tju.edu.cn (Jinwei HE)
Show less
History+
Received
Accepted
Published
2022-05-05
2022-08-31
2023-04-15
Issue Date
Revised Date
2023-01-13
PDF
(1953KB)
Abstract
In this paper, a fault-tolerant control method for an input-series output-parallel modular grid-tied pulse-width modulation (PWM) current source inverter is proposed to address the most commonly seen single symmetrical gate-commutated thyristor (SGCT) open-circuit fault problems. This method actively offsets the neutral point of the current space vector to ensure a sinusoidal output of the grid current, and it can achieve the upper limit power of the inverter under the condition of a single SGCT open-circuit fault. In addition, an active damping control method based on grid harmonic current feedback is proposed after analyzing the influence of the transformer ferromagnetic resonance caused by the neutral point offset on the power quality of the grid current. It has been demonstrated that the proposed method effectively suppresses the resonance caused by the transformer and the modified modulation, improving the grid current’s power quality.
As a large amount of renewable energy, such as wind and solar power, is widely applied in power generation, grid-tied inverter technology in power electronics has developed rapidly [1–3]. PWM current source inverters provide the advantages of simple structure and control, good short-circuit characteristics, and high output waveform quality; therefore, they have received increasing attention in new distributed generation systems, energy storage systems, power flow control [4–6]. With the increase in voltage and power levels, a single inverter cannot meet the requirements of system power capacity; therefore, research has been conducted on the modular current source inverter (CSI) and its control method [7,8].
Compared to a single CSI, a modular CSI has more power switches and thus has more potential for faults. The fault of the switches will not only cause serious distortion of the grid current waveform but also adversely affect the grid’s stability. Generally, the fault of switches can be divided into short-circuit fault and open-circuit fault [9]. In fact, open-circuit faults caused by the damage of the power switch itself and the loss of trigger pulses are more commonly observed. Therefore, it is of great theoretical and practical significance to study the open-circuit fault-tolerant control of modular CSI and ensure its upper limit power output under fault conditions.
A large number of open-circuit fault diagnosis and tolerant control methods have been proposed [10–15], but they primarily focus on voltage source converters (VSCs), such as cascaded H-bridges and T-type three-level inverters. In Ref. [10], a cascaded H-bridge converter with redundant modules was proposed, and the faulty module could be bypassed online using a switch. In Ref. [11], the fundamental output voltage of the cascaded H-bridge was controlled by looking up the offline table for the amplitude and phase angle, while the third and fifth harmonics were eliminated using specific harmonic elimination methods. In Ref. [12], the average line voltage deviation on the inverter side was compared with the threshold value during a sampling period to accurately diagnose IGBT (Insulated Gate Bibolar Transistor) open-circuit faults in T-type three-level inverters without adding additional hardware circuits.
Although fault-tolerant control methods for VSCs have been relatively mature, research on current source converters (CSCs) has primarily focused on optimizing modulation methods, power distribution, and common-mode voltage suppression [2–8]. There are still few studies on fault-tolerant control of CSC. Guo et al. [13] diagnosed short-circuit faults of a single or double SGCT (Symmetrical Gate-Commutated Thyristor) in CSC by calculating the average values of the feedback output currents and comparing them to the average absolute values of the current reference signals in one power frequency cycle, which can be simply implemented without additional sensors and other auxiliary detection devices. Fard et al. [14] diagnosed the open-circuit fault of current-source inverters in motor drives by the difference between the expected DC current from the PWM signals and the actual DC current and used the redundant branch to replace the faulty one. In Ref. [15], when the five-phase current-source inverter has a broken-line fault, the instantaneous active power fluctuation is reduced by reasonably setting the positive, negative, and pseudo-zero-sequence components of the line current and compensating the current offset of the LC filter, thereby improving the active power transmission capability of the inverter under broken-line faults.
Aiming at the single symmetrical gate-commutated thyristor (SGCT) open-circuit fault of input-series output-parallel modular grid-tied PWM CSI, this paper proposes a fault tolerant control method, which ensures the upper limit power by actively offsetting the neutral point of the reference current vector. Furthermore, based on the analysis of the influence of the transformer ferromagnetic resonance on the grid current, an active damping control method based on the grid harmonic current feedback is proposed to suppress the ferromagnetic resonance and improve the power quality of the grid current.
2 Fault-tolerant modulation of input-series output-parallel CSC
A typical input-series output-parallel modular CSI topology is illustrated in Fig.1. CSC1 and CSC2 are three-phase full-bridge modules composed of SGCT. Two modules are connected in series on the DC side, while on the AC side, they are connected in parallel through their respective LC filter and a Yy-Type three-winding transformer and then connected to the grid. The DC link current is and behaves as a current source. The upper and lower DC rail inductors of CSC1 are and respectively, the output PWM current of CSC1 is , and the capacitor and inductor of LC filter 1 are respectively and . The capacitor current is , and the inductor current is . In contrast, the upper and lower DC rail inductors of CSC2 are and respectively, the output PWM current is , and the capacitor and inductor of LC filter 2 are respectively and . The capacitor current is , and the inductor current is . The leakage inductors of the transformer windings connected to the two LC filters are and respectively, and the leakage inductor of the windings connected to the grid is . The three-phase grid voltage is and the grid current is . The transformer is mainly used to isolate the DC component of the output PWM current, which is explained in detail later. In addition, it can connect two inverters in parallel on the grid side and isolate the inverter from the grid to effectively reduce the common-mode voltage of the system.
According to the switching constraints of the CSC, only two switches are turned on at any time for each bridge, one in the upper and the other in the lower. Therefore, there are 81 switching states for the above input-series output-parallel CSC, and all the switching states can be divided into 19 PWM current vectors () according to the level of the total three-phase output PWM current (the sum of the CSC1 and CSC2 output PWM currents, which is +). The corresponding three-phase total-output PWM current levels and switching states are listed in Tab.1. In the table, the number of arrays represents the number of switches being turned on. For instance, the switching state (16:16) indicates that switches S1 and S6 of CSC1 and switches S1 and S6 of CSC2 are turned on.
Fig.2(a) shows the space vector diagram of the modular CSI under normal operating conditions. The three-phase instantaneous output PWM current is represented by a rotating reference current vector, , and the grid current can be controlled by adjusting . All the current vectors in Tab.1 can be utilized to synthesize based on the ampere-second balance principle, and is generally synthesized by three nearby vectors.
When the modular CSI has a single SGCT open-circuit fault, for instance, S1 in CSC1, A-phase output current of CSC1 cannot output the level owing to the S1 open-circuit fault; therefore, some switching states cannot be utilized to synthesize . All current vectors and switching states that cannot be utilized are marked in red font in Tab.1. It can be seen that and are not available, and and also lose some switching states, as shown in Tab.1.
The current space vector diagram for the S1 open-circuit fault condition is shown in Fig.2(b). After the loss of and , the reference current vector can only operate in the purple area in Fig.2(b). If the neutral point of the reference current vector is actively offset from point O to point O' and the reference current vector operates within the circle in Fig.2(b), the grid current can still be controlled as a sinusoidal output. In addition, the output power can be maximized under an S1 open-circuit fault condition. is the active offset vector and is the current reference vector with the O' point as the center of the circle trace after the active offset. is the current reference vector synthesized during the modulation and still centers at the O point. The three current vectors above satisfy:
where the active offset vector is:
Therefore, the normal modulation mode can be switched to the fault-tolerant modulation mode by actively offsetting the neutral point and superimposing the offset vector on . When rotates on the circle in Fig.2(b), the output PWM current of the modular CSI under a single-SGCT open-circuit fault condition is maximized, and the transmission power has an upper limit. At the same time, the modulation factor (ma) is 0.65, which is much larger than that when the faulty module is directly shut down. Notably, the marked operating circle in Fig.2(b) is the inscribed circle of the purple area, which represents the power transmission limit of the system under the condition of a single SGCT open-circuit fault. If the transmission power continues to increase, the operating circle will exceed the purple area, the output PWM current waveform will be distorted, and the desired power will not be output. Therefore, the fault-tolerant control method proposed in this study effectively improves the power transmission capability of the modular CSI and ensures the upper limit power output under open-fault conditions.
It should be noted that the active offset vector introduces a DC component into the three-phase output PWM current. However, its DC component cannot generate an alternating magnetic field in the transformer and, therefore, will not be transformed to the grid side. When other switches in the modular CSI have an open-circuit fault, the proposed fault-tolerant method can also be used; only the active offset vector is different. Tab.2 lists the expression of for all switches in the case of a single SGCT open-circuit fault.
3 Resonance analysis and control strategy
When a large DC current flows through the transformer, the core of the transformer transitions to the saturation region. However, capacitive components in the system are highly prone to ferromagnetic resonance with the nonlinear equivalent inductor of the transformer [16]. Ferromagnetic resonance not only distorts the grid current but also seriously endangers the stability of system operation [17]. Generally, ferromagnetic resonance is caused by fifth, seventh, or other low-order harmonics. Owing to the complex electromagnetic process involved in transformer ferromagnetic resonance, this study utilizes a harmonic current source to simply represent the effect of ferromagnetic resonance on the system instead of describing its process in detail. Considering ferromagnetic resonance, the single-phase equivalent circuit of the system is shown in Fig.3(a), where and are the internal resistances of the inductor. The Yy-Type three-winding transformer is represented by an ideal transformer and the corresponding winding leakage inductor, whereas a controlled current source represents the ferromagnetic resonance .The output currents of the two CSCs are first filtered by the LC filters and then added in parallel to obtain , which superimposes the harmonic current and flows into the grid; thus, a grid current with large harmonic content is generated. Moreover, the content of the fifth and seventh harmonics in the output current increases under fault conditions owing to the decreaseof ma, which also affects the power quality of the grid current.
For further analysis, the equivalent circuit of the system is first simplified. Assuming that the two LC filters have the same parameters and the transformer windings connected to the LC filters also have exactly the same leakage inductor, that is, ===, and =. Ignoring the transformer’s voltage transformation function, the equivalent circuit shown in Fig.3(a) can be simplified to the equivalent circuit in Fig.3(b), where
Two CSIs that first pass through their respective LC filters and then connect in parallel are completely equivalent to those first connected in parallel and then passing through a common LC filter.
To suppress LC resonance in CSC, the capacitor voltage or inductor voltage is generally used as the inner-loop feedback, which is equivalent to a virtual resistance connected in parallel to the capacitor or inductor [18]. However, this method cannot be used to suppress the ferromagnetic resonance of transformers. An active damping method based on grid harmonic current feedback is proposed in this paper, and the system control block diagram combined with the proposed fault-tolerant modulation strategy is shown in Fig.4.
First, the three-phase grid current is transformed from the three-phase stationary frame to the αβ frame to obtain and . Subsequently, and are compared with the reference currents and , and the difference is used as the input of the PR controller to control the fundamental current. Feedforward control is implemented from the reference current to the modulation input to improve the system’s dynamic response. Therefore, the fundamental current modulation inputs and are produced by
where and are the proportional and resonant gains of the PR controller, respectively, is the bandpass frequency of the resonant controller, is the fundamental angular frequency.
Second, the grid current is filtered by a high-pass filter with a cutoff frequency :
Multiplying by the feedback coefficient , we obtain the damping current , which is also the harmonic current modulation input and .
Then, two modulation inputs are added to obtain the final reference currents and and transformed from the αβ frame back to the three-phase stationary frame to produce the reference current , which can be utilized for space vector modulation (SVM) according to the modulation mode. When the system is in normal operation, the reference current can be directly utilized for modulation. When the system has a single SGCT open-circuit fault, is added to the reference current . can be obtained from Tab.2 based on the faulty switch.
Finally, the current vector is selected to generate the corresponding gate signal based on the ampere-second balance principle, which controls the turn-on and turn-off of CSI power switches.
Fig.5 shows the transfer function diagram of the system after introducing active damping control. Transformer ferromagnetic resonance is represented by a seventh harmonic current source, and its equivalent transfer function GIh can be expressed as
where and are the harmonic gain, harmonic angular frequency, and bandpass frequency, respectively. The active damping loop gain is expressed as follows:
The other transfer functions are expressed according to the equivalent circuit shown in Fig.3(b) as follows:
Therefore, the system transfer function can be expressed as
where
To analyze the suppression effect of the proposed active damping control method on the ferromagnetic resonance and LC filter resonance, the closed-loop Bode diagram of the system with different feedback coefficients k is plotted, as shown in Fig.6–Fig.8. Fig.6 shows the closed-loop Bode diagram of the transfer function / when k increases from 0 to 0.2. When active damping control is not introduced, a large resonance peak appears at approximately 350 Hz, which is close to the ferromagnetic resonance frequency of the transformer. As the feedback coefficient k increased, the ferromagnetic resonance peak gradually decreased, and the ferromagnetic resonance was effectively suppressed. When k is sufficiently large, the ferromagnetic resonance peak decreases significantly, and the active damping effect is highly effective.
Closed-loop Bode diagrams of the transfer functions / and / are shown in Fig.7 and Fig.8, respectively. When k = 0, a resonance peak appears at approximately 350 Hz. With an increase in k, the resonant peak of the system gradually decreased, the resonant peak frequency decreased slightly, and the system had a larger bandpass frequency. However, when k is sufficiently large, it causes a large phase shift between the fundamental and resonant frequencies.
Therefore, the active damping control method proposed in this study has a positive damping effect on the ferromagnetic resonance of the transformer. 0.1 is chosen as the feedback coefficient k in this study to have a significant damping effect.
4 Simulation results
A simulation model was built for simulation verification in MATLAB/Simulink to verify the effectiveness of the proposed fault-tolerant modulation and active damping method. The key simulation parameters are listed in Tab.3. The modular CSC transmits a constant active power of 48 kW and operates with a unit power factor under healthy operating conditions. In the case of a single SGCT open-circuit fault, the transmitted active power must be reduced; however, the unit power factor is still maintained. The ferromagnetic resonance was simulated using a harmonic-controlled current source.
The simulation is divided into four stages to verify the proposed fault-tolerant modulation and active damping methods. A brief description of these four stages is given in Tab.4, and the full-stage simulation results are shown in Fig.9.
Stage 1: 0.16–0.2 s, the system operates healthy without any fault. The grid current is approximately 70 A, of great quality, and in the same phase angle as the grid voltage, and the total harmonic distortion (THD) is only 2.08%. The total three-phase output current was a symmetrical five-level PWM current.
Stage 2: 0.2–0.26 s, the system operates under a single SGCT open-circuit fault condition, but fault-tolerant control is not enabled. The grid current of the faulty phase (phase A) is seriously distorted with a THD of 23.08%, and the upper peak is cut off, whereas the grid currents of the non-faulty phases (phases B and C) also have a certain degree of distortion. The total output current of the faulty phase (phase A) changes into four asymmetric levels, whereas the total output current of the non-faulty phases (phases B and C) has more levels. It should be noted that when a single SGCT open-circuit fault occurs without any fault-tolerant control, the switching constraints of the CSC will not be satisfied; therefore, it is not allowed to operate in this case in practice.
Stage 3: 0.26–0.32 s, The system switches to fault-tolerant modulation without an active damping control. The introduction of an active offset vector restored the grid current of the faulty phase (phase A) to a sinusoidal waveform. However, the ferromagnetic resonance of the transformer and the decrease in ma cause an increase in the harmonic content of the grid current, and the THD of the faulty phase grid current reaches 28.86%. In addition, the active offset vector makes all three phases of the total output current asymmetric.
Stage 4: 0.32–0.38 s, Active damping control is introduced. The resonance was quickly damped, and the grid current entered a new steady state after approximately 30 ms. At this time, the THD of the A-phase grid current decreases to 3.82%. The grid current was only 58 A, owing to the reduced power after the fault-tolerant control. At the same time, the decrease in ma results in more fifth and seventh harmonics in the output current [19]; therefore, the quality of the grid current waveform decreases slightly compared to that under normal operation.
To further verify the effectiveness of the proposed method, we carried out hardware-in-the-loop simulations, and the detailed circuit and control parameters in the hardware-in-the-loop simulation are listed in Tab.5.
The steady state of performance using the proposed method in the case of both healthy operations without any fault and fault operation with a single IGCT open circuit is shown in Fig.10. It can be observed that the grid current has high quality with a low THD of 2.54%, and the three-phase PWM output current is a symmetrical five-level waveform in the case of a healthy operation. In the case of faulty operation with a single IGCT open-circuit, the amplitude of the grid current decreased from 29 to 23 A due to the limited power transmission capacity of the CSC. Simultaneously, the THD of the grid current decreased slightly to 4.28%. It is evident that although the output current has only an asymmetrical four-level, the proposed method could still realize the sinusoidal output of the grid current and ensure waveform quality under the single IGCT fault condition.
The dynamic response of CSC during the control method switches is shown in Fig.11. The proposed method has been verified via a total of three stages, in which at stage 1, the CSC operates without any faults; stage 2 switches to the proposed fault-tolerant modulation method without adding active damping control, whereas, at stage 3, the fault-tolerant modulation method is maintained and active damping control is added.
In stage 1, the grid current is sinusoidal because no faults occur. In stage 2, CSC switches to fault-tolerant modulation without active damping control. Although the neutral point of the current space vector is actively offset to maintain a sinusoidal output, the ferromagnetic resonance of the transformer causes severe distortion of the three-phase grid current with a THD of 67.2%. This is because the effect of the transformer ferromagnetic resonance was intentionally increased in the hardware-in-the-loop simulation. In stage 3, with the introduction of active damping control, the ferromagnetic resonance of the transformer is gradually suppressed, and the transient process is only 40 ms. Due to the power transmission capacity limitation and the modulation factor ma reduction, both the amplitude and quality of the grid current decrease.
The dynamic performance of the proposed method in the case of grid voltage dips is shown in Fig.12. When the grid voltage drops by 0.2 pu, the grid current is slightly distorted in the transient process, but the system enters a new steady state after only 25 ms. It should be noted that when the CSC operates using the proposed fault-tolerant control method under the single IGCT open-circuit fault condition, the modulation factor of the CSC is already close to the maximum value; therefore, the grid current will not increase, and the transmission power will be further reduced.
5 Conclusions
This study proposes a fault-tolerant control method for input-series output-parallel modular CSCs with a single SGCT open-circuit fault, which achieves a sinusoidal output of the grid current under fault conditions by actively offsetting the output current space vector neutral point. In addition, to suppress the transformer ferromagnetic resonance, an active damping control method with grid harmonic current feedback was proposed to ensure the quality of the grid current.
However, it should be noted that the proposed method can only be applied to two CSC modules with input-series and output-parallel topologies, and the system’s scalability is limited to a certain extent. Therefore, it is necessary to further research the fault-tolerant control of multiple CSC modules with input-series, output-parallel, and other topologies and to propose a general fault-tolerant control method applied to various modular CSC topologies.
Guo X, Yang Y, Zhu T. ESI: a novel three-phase inverter with leakage current attenuation for transformerless PV systems. IEEE Transactions on Industrial Electronics, 2018, 65(4): 2967–2974
[2]
Sahan B, Araújo S V, Nöding C. . Comparative evaluation of three-phase current source inverters for grid interfacing of distributed and renewable energy systems. IEEE Transactions on Power Electronics, 2011, 26(8): 2304–2318
[3]
KumarG RBandaruR K. Single phase PV-fed current source inverter with sinusoidal grid current injection control. In: 2019 International Conference on Electrical, Electronics and Computer Engineering (UPCON), Aligarh, India
[4]
Wei Q, Wu B, Xu D. . An optimized strategy for PWM current source converter based wind conversion systems with reduced cost and improved efficiency. IEEE Transactions on Power Electronics, 2018, 33(2): 1202–1210
[5]
Wu B, Pontt J, Rodriguez J. . Current-source converter and cycloconverter topologies for industrial medium-voltage drives. IEEE Transactions on Industrial Electronics, 2008, 55(7): 2786–2797
[6]
Wei Q, Wu B, Xu D. . A new configuration using PWM current source converters in low-voltage turbine-based wind energy conversion systems. IEEE Journal of Emerging and Selected Topics in Power Electronics, 2018, 6(2): 919–929
[7]
XuDZargariN RWuB, . A medium voltage AC drive with parallel current source inverters for high power applications. In: 2005 IEEE 36th Power Electronics Specialists Conference, Dresden, Germany
[8]
He J, Li Q, Zhang C. . Quasi-selective harmonic elimination (Q-SHE) modulation-based DC current balancing method for parallel current source converters. IEEE Transactions on Power Electronics, 2019, 34(8): 7422–7436
[9]
Lu B, Sharma S K. A literature review of IGBT fault diagnostic and protection methods for power inverters. IEEE Transactions on Industry Applications, 2009, 45(5): 1770–1777
[10]
Neyshabouri Y, Iman-Eini H. A new fault-tolerant strategy for a cascaded H-bridge based STATCOM. IEEE Transactions on Industrial Electronics, 2018, 65(8): 6436–6445
[11]
Song W, Huang A Q. Fault-tolerant design and control strategy for cascaded H-bridge multilevel converter-based STATCOM. IEEE Transactions on Industrial Electronics, 2010, 57(8): 2700–2708
[12]
Chen Y, Du L, He J. Online diagnosis and ride-through operation for cascaded H-bridge converter based STATCOM with a single open-circuit IGBT. IEEE Transactions on Industrial Electronics, 2022, 69(8): 7549–7559
[13]
Guo X, Sui S, Wang B. . A current-based approach for short-circuit fault diagnosis in closed-loop current source inverter. IEEE Transactions on Industrial Electronics, 2020, 67(9): 7941–7950
[14]
FardM THeJWangZ. Fault diagnosis and fault-tolerant operation of current source inverter for safety-critical applications. In: 2020 IEEE Transportation Electrification Conference & Expo, Chicago, IL, USA
[15]
He J, Lyu Y, Li Q. . A fault-tolerant operation approach for grid-tied five-phase current-source converters with one-phase supplying wire broken. IEEE Transactions on Power Electronics, 2019, 34(7): 6200–6218
[16]
GerberI PMwanikiF MVermeulenH J. Parameter estimation of a Ferro-resonance damping circuit using pseudo-random impulse sequence perturbations. In: 2021 56th International Universities Power Engineering Conference (UPEC), Middlesbrough, UK
[17]
Abdelazim Mellik T, Painter F D, Shipp D D. . Proactive study and novel mitigation of MV power system damage due to sub-power-frequency Ferro-resonance for a gas plant. IEEE Transactions on Industry Applications, 2018, 54(4): 3991–4000
[18]
Li Y. Control and resonance damping of voltage-source and current-source converters with LC filters. IEEE Transactions on Industrial Electronics, 2009, 56(5): 1511–1521
[19]
WuB. High-Power Converters and AC Drives. New York: Wiley-IEEE Press, 2006
RIGHTS & PERMISSIONS
Higher Education Press 2022
AI Summary 中Eng×
Note: Please be aware that the following content is generated by artificial intelligence. This website is not responsible for any consequences arising from the use of this content.