1. School of Electrical Engineering, Shenyang University of Technology, Shenyang 110870, China
2. Warwick Manufacturing Group, University of Warwick, Coventry CV4 7AL, Warwick, UK
3. School of Electrical Engineering, Shandong University, Jinan 250061, China
wby-js@163.com
Show less
History+
Received
Accepted
Published
2020-01-15
2020-08-06
2023-02-15
Issue Date
Revised Date
2020-12-10
PDF
(5270KB)
Abstract
To improve the fault redundancy capability for the high reliability requirement of a brushless doubly-fed generation system applied to large offshore wind farms, the control winding of a brushless doubly-fed reluctance generator is designed as an open-winding structure. Consequently, the two ends of the control winding are connected via dual three-phase converters for the emerging open-winding structure. Therefore, a novel fault-tolerant control strategy based on the direct power control scheme is brought to focus in this paper. Based on the direct power control (DPC) strategy, the post-fault voltage vector selection method is explained in detail according to the fault types of the dual converters. The fault-tolerant control strategy proposed enables the open-winding brushless doubly-fed reluctance generator (BDFRG) system to operate normally in one, two, or three switches fault of the converter, simultaneously achieving power tracking control. The presented results verify the feasibility and validity of the scheme proposed.
Shi JIN, Long SHI, Sul ADEMI, Yue ZHANG, Fengge ZHANG.
Fault-tolerant control of an open-winding brushless doubly-fed wind power generator system with dual three-level converter.
Front. Energy, 2023, 17(1): 149-164 DOI:10.1007/s11708-020-0711-2
The brushless doubly-fed generator (BDFG) has the advantages of brushless structure, easiness in variable-speed constant-frequency operation, flexibly controllable active and reactive powers, and low converter capacity and cost, thus, suitable for wind power generation, especially the large offshore wind turbines/farms [1–6]. In a wind power generation system, the converter may fail due to the high energy density, complex conditions, and the relatively low reliability of power switches, which raises the concern about the reliability of BDFG [7–9]. The problem of improving system reliability can be tackled by improving the performance of the standard topologies and the early/post diagnostics of power devices [10,11] or developing new fault-tolerant topologies of power drives. Various converter structures for post-fault operation have been studied. A comparative performance study of the split-capacitor (SC) topology, the extra-leg split-capacitor (ELSC) topology and the extra-leg extra-switch (ELES) topology for voltage model (VM)-based direct torque control (DTC) brushless alternating current (BLAC) drives has been presented in Ref. [12]. In Ref. [13], many fault tolerant three-phase AC motor drive topologies are compared, including the switch-redundant topology, the double switch-redundant topology, the phase-redundant topology, the cascaded inverter topology, and the four-leg inverter topology. In a back-to-back converter, the phases of both sides (grid/machine) can be connected to each other through triacs [14]. In Ref. [14], a fault tolerant back-to-back converter for doubly-fed induction generator (DFIG)-based wind energy conversion application is studied. After the fault occurrence in one of the switches, the converter will continue its operation with the remaining five healthy legs. Proper gate signals are calculated and generated based on the actual five-leg structure and the vector control strategy. The multilevel converter is also an effective solution for fault tolerance because of more additional switching states. A novel active fault-tolerant space vector pulse width modulation (SVPWM) strategy for single-phase faults in three-phase multilevel converters is proposed in Ref. [15]. The multilevel converter is treated as a two-level converter (2LC) by introducing an offset vector. Its SVPWM strategy is designed according to the post-fault topology of the hybrid input switched seven-level converter. As a special multi-level converter structure, the dual converter topology connected to an open-winding machine has been discussed and applied in fault tolerant control. In Ref. [16], a method that allows the operation with direct torque control (DTC) in incipient faults of the power switching devices in single dc-link dual inverters is proposed. The control algorithm makes use of additional states to maintain control of the induction machine. In Ref. [17], a fault tolerant control strategy when faults occur in paralleled inverters fed permanent magnet synchronous motor (PMSM) drives is studied. It fully uses all the healthy phase legs including those in faulty inverters. The control scheme is based on rotor flux-oriented vector control and paralleled inverter structure.
Overall, the use of multilevel converters and dual converter structures has become an effective solution for post-fault operation of motor/generator systems for the following reasons. Compared to the traditional 2LC, the multilevel converter has the advantages of smaller output harmonic content, flexible control, small voltage stress on the switches, and lower loss. The open-winding topology has the advantages of non-neutral voltage fluctuation, smaller converter capacity, and stronger fault-tolerant capability [18,19]. Generally, the above topology can be applied to various systems, but the control strategies for post-fault operation are not universal. The post-fault operation strategies are usually obtained by modifying the original strategies (such as flux/voltage-oriented control, DTC) based on the converter topology after fault. Therefore, various systems with corresponding original control strategies have different strategies for post-fault operation. In this paper, the open-winding structure with dual three-level converter (3LC) is applied to the BDFRG system for wind power generation. All six terminals of control winding (CW) are drawn out to connect with the dual 3LC while power winding (PW) is grid connected. Besides, a post-fault operation strategy based on direct power control (DPC) is discussed. Due to the more switching states produced by dual 3LC, the vector selection method in the control strategy is more diversified, and the possibility of post-fault operation is significantly increased. Moreover, synthesized space voltage vector distributions of the dual 3LC are analyzed in detail when one switch open-/short-circuit fault occurs and two/three switches fault occur. The faulty switches are put under trigger suppression (no longer divided into open-circuit or short-circuit fault) to regain operation when more than one switch fault occur, which can simplify the analysis and system design. Based on the DPC strategy, the post-fault voltage vector selection method is explained in detail according to the fault types of the dual 3LC. A power deviation comparison module is designed to more appropriately select the voltage vector. The control strategy proposed can enable the open-winding brushless doubly fed reluctance generator (OW-BDFRG) system to operate without interruption when one, two, or three switches fault occurs in the dual 3LC, and simultaneously implement the power tracking control. The feasibility and validity of the fault-tolerant control strategy proposed based on DPC for the OW-BDFRG are analyzed and verified.
2 Mathematical model of OW-BDFRG
The space vector equations of voltages and fluxes for the OW-BDFRG in rotating reference frames are expressed as [1]
where Rp and Rc are the resistances of PW and CW; Lp and Lc are the self-inductances of PW and CW; Lpc is the mutual inductance between PW and CW; up, ip, and λp is the respective space voltage, current, and flux vectors of PW in the PW rotating reference frame; uc, ic, and λc is the respective space voltage, current and flux vectors of the CW in the CW rotating reference frame; and ωr is the rotor electrical angular velocity. It should be noted that the space vector equations of the power and control windings are expressed in two different reference frames, the PW dp–qp reference frame rotating in arbitrary angular velocity ω and the CW dc–qc reference frame rotating at angular velocity . The CW flux linkage can be expressed in Eq. (5) by substituting Eq. (3) into Eq. (4).
where .
The electromagnetic torque of the OW-BDFRG is given as
where λpc is the PW flux linking CW, and , but its rotational angular velocity is the same as CW flux. The mechanical power of the OW-BDFRG can be expressed as [1,2]
where ωp and ωc are the applied frequencies to PW and CW respectively, and pr is the rotor pole number. Neglecting the copper losses and the changes in field energy, the instantaneous electrical power becomes approximately the same as mechanical i.e., Pp≈ Ppm. Consequently, a method similar to torque control can be used to control power [20,21]. The rotor speed can be written as
The synchronous speed is defined, as expressed in Eq. (9) (control winding frequency is equal to 0).
3 Topology of OW-BDFRG fault-tolerant control
The structural diagram of the OW-BDFRG system is shown in Fig. 1. The machine side converter 1 (MSC1) and machine side converter 2 (MSC2) are both neutral point clamped (NPC) type 3LC and C1, C2, C3, C4 are equivalent capacitors. The OW-BDFRG stator comprises of two sets of windings with different pole numbers, the PW for generation and CW for excitation. The coupling relationship between the two sets is realized by the special rotor. The CW of OW-BDFRG is designed as the open-winding structure. The CW is opened and its two ends are connected with dual three-level bidirectional converter with the isolated DC bus connection mode, which avoids the flow of zero-sequence current.
According to Fig. 1, the phase voltage of the CW can be expressed as
To ensure normal operation of the generator, the sum of the three-phase voltages of the CW should be zero [22], thus, the CW phase voltage can be expressed as
In DPC, the active power (Pp) and reactive power (Qp) of PW is controlled by adjusting the rotation and amplitude of λc which is regulated by uc. In normal operation, the DPC principle of a common BDFRG system can be summarized as [20]: If λc lies in the kth sector, then vectors Uk+1 or Uk+2 would increase Pp, while Uk−1 or Uk−2 would decrease it (Fig. 2(a)). In the same sector, Uk−1, Uk, or Uk+1 would decrease Qp, while Uk+2, Uk+3, or Uk−2 would increase it (Fig. 2(a)). Compared with 2LC, 3LC provides more available voltage vectors (Fig. 2(b)). P, O and N represent the three different output states of single-phase bridge arm. Taking the a-phase of MSC1 as an example, the output state of the a-phase in MSC1 is set as P when Sa1 and Sa2 are opened. The output state is set as O when Sa2 and Sa3 are opened. When Sa3 and Sa4 are opened, the output state is set as N. When CW is connected to dual 3LC, uc is determined by three kinds of switching states in each phase of dual 3LC, and it can be synthesized by the voltage vectors output by MSC1 and MSC2 respectively. Nine switching states are present in each phase of dual 3LCs. Therefore, the amount of switching state combination is 93 = 729, corresponding to 61 different space voltage vectors ultimately. In the above case, the effective voltage vectors for DPC are no longer limited to six (Fig. 2(a)), and the division of sectors can also be more detailed, as described in Section 4.
4 Fault analysis and voltage vector selection
Block diagram of the system proposed is demonstrated in Fig. 3. Switch fault diagnosis has been extensively studied, which is not the focus of this paper. This paper contemplates and focuses on the post-fault operation of the system, considering one, two, and three switches fault.
In Fig. 3, Pp and Qp are expressed as
The αβ-axis component of λc and its angle can be determined respectively as
Since θ ranges from –π/2 to π/2, θ is not the true position angle of CW, thus the CW flux angle needs to be corrected and revised as listed in Table 1.
4.1 Fault of one switch
Take the switch fault on the a-phase of MSC1 as the case of one switch fault. There are 8 types of one switch faults on a-phase arm of MSC1, which consist of Sa1 open-/short-circuit fault, Sa2 open-/short-circuit fault, Sa3 open-/short-circuit fault, and Sa4 open-/short-circuit fault.
4.1.1 Sa2 in short-circuit fault/Sa4 in open-circuit fault
If the output state of the a-phase arm is N, then a current loop is formed by Sa2–Sa3–Sa4–C2–VDa1 when the short-circuit fault of Sa2 occurs. Thus, to avoid secondary failures, the output state N is forbidden under this circumstance. When the open-circuit fault of Sa4 occurs, the output state N of the a-phase arm cannot be produced, hence it is lost. In both cases, the synthesized space voltage vector distribution of MSC1 and MSC2 is depicted in Fig. 4, where the voltage vectors used for DPC are indicated in blue. Ua-b represents the synthesized space voltage vector of the voltage vector Ua produced by MSC1 and Ub produced by MSC2. The red dots represent the voltage vectors that cannot be synthesized. The diversification of voltage vector selection makes the adjustment of Pp and Qp more flexible and effective. Thus, to precisely utilize more voltage vectors, the sector plane is divided into 18 sectors as depicted in Fig. 4. Compared with the DPC scheme on the traditional 2LC, the CW voltage vector selection method is more diversified at this time. Hence, when CW flux linkage is located in sector II, the CW voltage vector located in region 1 can increase Pp and reduce Qp. The CW voltage vector located in region 2 increases both Pp and Qp. On the other hand, the CW voltage vector located in region 3 can reduce Pp and increase Qp, while the CW voltage vector in region 4 can reduce Pp and Qp. As illustrated above, when the CW flux linkage is located in sector II, U14-8, U14-9, and U15-9 can increase Pp and reduce Qp, but their effects are not consistent. U15-9 has a stronger regulation effect on Pp than U14-8 and U14-9, on the contrary, U15-9 has a weaker regulation effect on Qp than U14-8 and U14-9. When CW is in other sectors, the influence of voltage vector on power can be analogous.
This paper focuses on adjusting Pp and Qp by designing the power deviation comparison module in Fig. 5. According to DPC principles, the switching voltage vector selection table is reconstructed as tabulated in Table 1. S1 is set as 1 when DPp≥threshold, and S1 is set as 0 when DPp≤−threshold. Similar rules apply to S2, while S3 is employed to represent the numerical relationship between the errors of the active and reactive powers. S3 is set as 1 when the error of the active power is more than that of the reactive power, and the selected voltage vector accelerates the change in the active power more effectively. Otherwise, S3 is set at 0, and the selected voltage vector accelerates the change in the reactive power more effectively.
4.1.2 Sa3 in short-circuit fault/Sa1 in open-circuit fault
If the output state of the a-phase arm is P, a current loop is formed by Sa1–Sa2–Sa3–VDa2–C1 when the short-circuit fault of Sa3 occurs. To avoid secondary failures, the output state P is forbidden under this circumstance. When the open-circuit fault occurs in Sa1, the output state P of the a-phase arm cannot be produced, thus, it is lost. In both cases, the synthesized space voltage vector distribution of MSC1 and MSC2 is depicted in Fig. 6 where the voltage vectors used for control are indicated in blue, and the red points represent the voltage vectors that cannot be synthesized. The voltage vector selected are the same as that in Fig. 4, hence the switching voltage vector selection is the same as that in Table 2.
4.1.3 Sa2 in open-circuit fault
When the open-circuit fault of Sa2 occurs, the output state P and O of the a-phase arm cannot be produced. The synthesized space voltage vector distribution of MSC1 and MSC2 is depicted in Fig. 7, under this circumstance. The synthesized space voltage vectors used for DPC are indicated in blue, while the voltage vectors that cannot be synthesized are presented in red dots (Fig. 7). The entire space plane is evenly subdivided into 12 sectors in Fig. 7, while the switching voltage vector selection table is given in Table 3.
4.1.4 Sa3 in open-circuit fault
When the open-circuit fault of Sa3 occurs, the output state N and O of the a-phase arm cannot be produced. The synthesized space voltage vector distribution of MSC1 and MSC2 are depicted in Fig. 8. The voltage vectors used for DPC are indicated in blue, while the voltage vectors that cannot be synthesized are represented in red dots (Fig. 8). The voltage vector selection is the same as that in Fig. 7, thus the switching voltage vector selection table is the same as that in Table 3.
4.1.5 Sa1 or Sa4 in short-circuit fault
When the short-circuit fault of Sa1 or Sa4 occurs, the output state O is forbidden in order to prevent capacitor C1 or C2 from short-circuit. The synthesized space voltage vector distribution of MSC1 and MSC2 are illustrated in Fig. 9, where the synthesized space voltage vectors employed for the DPC are indicated in blue. It is important to mention that there is no non-synthetic vector in both cases. However, to simplify the design of the fault-tolerant strategy, the same voltage vector selection method is employed as shown in Figs. 4 and 6. Although this method reduces the bus voltage utilization compared to normal operation, the overall voltage vector selection table design of the system is more concise as compensation.
4.2 Fault of two switches
Once the fault of two or more switches is detected (whether open-circuit or short-circuit fault), the fault switches are put under trigger suppression to regain operation, which reduces the complexity of the analysis and system design. In this paper, the fault conditions of the following two switches are analyzed separately: two switches on one phase of one converter (Sa1 and Sa2, Sa1 and Sa3, Sa1 and Sa4, Sa2 and Sa3, Sa2 and Sa4, Sa3 and Sa4), two switches on two phases of one converter (Sa1 and Sb1, Sa1 and Sb2, Sa1 and Sb3, Sa1 and Sb4, Sa2 and Sb1, Sa2 and Sb2, Sa2 and Sb3, Sa2 and Sb4), and two switches on two phases of two converters (Sa1 and Sd1, Sa1 and Sd2, Sa1 and Sd3, Sa1 and Sd4, Sa2 and Sd1, Sa2 and Sd2, Sa2 and Sd3, Sa2 and Sd4 fault). The synthesized space voltage vector distributions of MSC1 and MSC2 in the above cases are shown in Fig. 10, in which the vectors that cannot be synthesized are represented in red dots, and the vectors that can be used for control are indicated in blue.
It is worth noting that the a-phase arm of MSC1 cannot output the P, N, and O state when the following faults occur: Sa1 and Sa3 fault, Sa2 and Sa3 fault, Sa2 and Sa4 fault. This means that MSC1 cannot output the effective voltage vector and the synthesized voltage vectors cannot be produced. MSC1 and MSC2 cannot produce the suitable composite vector when the following faults occur: Sa2 and Sb3 fault, Sa2 and Sd3 fault. Thus, the system cannot operate normally by adopting the strategy proposed when the above faults occur.
The voltage vector that can be used for control is the same as that in Figs. 4, 6, and 9 when the following faults occur: Sa1 and Sb1, Sa1 and Sd1, Sa1 and Sa4. The voltage vector that can be used for control is the same as that in Figs. 7 and 8 when the following faults occur: Sa1 and Sb2, Sa1 and Sb4, Sa1 and Sd2, Sa1 and Sd4, Sa2 and Sb1, Sa2 and Sb2, Sa2 and Sd1, Sa2 and Sd2, Sa1 and Sa2, Sa3 and Sa4. For simplicity and readability, the voltage vector selection table with the same available vectors as that in Section 4.1 is no longer repeated. This section only gives the voltage vector selection tables (Tables 4–7) in the following faults: Sa1 and Sb3, Sa1 and Sd3, Sa2 and Sb4, Sa2 and Sd4. The available voltage vectors in these cases are different from those described in Section 4.1. The system can still operate stably under the action of these voltage vectors.
4.3 Fault of three switches
The conditions of fault of three switches are analyzed separately: fault of three switches on one phase of one converter (Sa1, Sa2 and Sa3; Sa1, Sa2 and Sa4), fault of three switches on two phases of one converter (Sa1, Sa2 and Sb1; Sa1, Sa2 and Sb2; Sa1, Sa2 and Sb3; Sa1, Sa2 and Sb4; Sa2, Sa3 and Sb1; Sa2, Sa3 and Sb2; Sa2, Sa3 and Sb3; Sa2, Sa3 and Sb4), fault of three switches on two phases of two converters (Sa1, Sa2 and Sd1; Sa1, Sa2 and Sd2; Sa1, Sa2 and Sd3; Sa1, Sa2 and Sd4, Sa2, Sa3 and Sd1; Sa2, Sa3 and Sd2; Sa2, Sa3 and Sd3; Sa2, Sa3 and Sd4), fault of three switches on three phases of one converter (Sa1, Sb1 and Sc1; Sa1, Sb1 and Sc2; Sa1, Sb1 and Sc3; Sa1, Sb1 and Sc4; Sa1, Sb2 and Sc1; Sa1, Sb2 and Sc2; Sa1, Sb2 and Sc3; Sa1, Sb2 and Sc4; Sa2, Sb2 and Sc1; Sa2, Sb2 and Sc2; Sa2, Sb2 and Sc3; Sa2, Sb2 and Sc4), and fault of three switches on three phases of two converters (Sa1, Sb1 and Sd1; Sa1, Sb1 and Sd2; Sa1, Sb1 and Sd3; Sa1, Sb1 and Sd4; Sa1, Sb2 and Sd1; Sa1, Sb2 and Sd2; Sa1, Sb2 and Sd3; Sa1, Sb2 and Sd4; Sa2, Sb2 and Sd1; Sa2, Sb2 and Sd2; Sa2, Sb2 and Sd3; Sa2, Sb2 and Sd4).
The synthesized space voltage vector distributions of MSC1 and MSC2 in the above cases are shown in Fig. 11. It is worth noting that the a-phase arm of MSC1 cannot output the P, N and O state when the following faults occur: Sa1, Sa2 and Sa3; Sa1, Sa2 and Sa4; Sa2, Sa3 and Sb1; Sa2, Sa3 and Sb2; Sa2, Sa3 and Sb3; Sa2, Sa3 and Sb4; Sa2, Sa3 and Sd1; Sa2, Sa3 and Sd2; Sa2, Sa3 and Sd3; Sa2, Sa3 and Sd4. This means that MSC1 cannot output the effective voltage vector and the synthesized space voltage vectors cannot be produced. MSC1 and MSC2 cannot produce the suitable composite vector when the following faults occur: Sa1, Sa2 and Sb3; Sa1, Sa2 and Sd3; Sa1, Sb2 and Sc3; Sa2, Sb2 and Sc3; Sa1, Sb2 and Sd2; Sa2, Sb2 and Sd2; Sa2, Sb2 and Sd3. Thus, the system cannot operate normally by adopting the strategy proposed when the above faults occur.
The available voltage vectors in other cases are the same as those described in Sections 4.1 and 4.2. There is no doubt that the system can operate reliably under the control of these vectors. The simulation results of this part are omitted for simplicity.
5 Simulation results
The control strategy proposed (Fig. 3) for the OW-BDFRG is emulated and implemented using Matlab/Simulink. The generator parameters are: nominal power 23 kW, the number of pole-pairs are PW-4 and CW-2 respectively. The resistances of PW and CW are 0.3871 W and 0.3773 W respectively, self-inductances of PW and CW are 69.46 mH and 59.25 mH respectively, while the mutual-inductance between the two-stator windings is 56.52 mH. During simulation, the threshold of the active and the reactive power hysteresis comparator is 0.1 kW and 0.1 kvar, respectively. The PW is grid connected as evidenced in Fig. 1 (i.e., voltage amplitude is V and frequency is 50 Hz). The DC-link voltage is set at 60 V (Udc1 = Udc2 = 60 V). The switch state is set to 0 to imitate open-circuit fault and 1 to imitate short-circuit fault, respectively. C1 = C2 = C3 = C4 = 2500 mF.
5.1 Operation without fault-tolerant control
The failure in power switches will affect the performance of the system and completely paralyze the system in severe cases. Taking the fault of Sa2 open-circuit as an example, the transitional response from healthy mode to fault mode is simulated as illustrated in Figs. 12 and 13. The fault occurred during the sub-synchronous speed operation is shown in Fig. 12. The system runs normally in the regular DPC scheme prior to 0.7 s and 2.5 s respectively. When the fault occurs, the PW and CW current are distorted irregularly, thus Pp and Qp cannot track the set point and have a huge deviation.
Figure 13 illustrates the fault occurred during the super-synchronous speed operation. In healthy mode, when the OW-BDFRG is in sub-synchronous operation, the maximum active power deviation is less than 0.2 kW, and the maximum reactive power deviation is less than 0.1 kvar. However, when the system is operating super-synchronously, the maximum active power deviation is less than 0.5 kW, and the maximum reactive power deviation is less than 0.1 kvar.
5.2 Fault-tolerant operation
To verify the effectiveness of the fault-tolerant control proposed, the control method proposed is scrutinized in different fault types as discussed in Section 4. During simulation, the reference speed (nrref), active power reference (Ppref) and reactive power reference (Qpref) change stepwise at different times as shown in Fig. 14. The reference value of the active power is wind speed dependent; thus, the reference value of the reactive power needs to meet the power factor requirement of the grid. The power here is only given in the form of simulation to illustrate the effectiveness of the method (i.e., the negative sign - refers to generating active power and reactive power). The results presented include PW/CW currents, active/reactive power, and sector calculation.
Figures 15–26 show the steady and dynamic results for post-fault operation corresponding to different faults. The OW-BDFRG operates at sub-synchronous speed, synchronous speed, and super-synchronous speed respectively in different time periods to verify the variable-speed constant-frequency operation characteristics of the system. Ppref and Qpref generate step changes at different times to observe power tracking. It is illustrated from the PW current that the PW current frequency is always 50 Hz regardless of whether the OW-BDFRG is running in sub-synchronous, synchronous, or super-synchronous operation. Moreover, it is shown that the PW current is sinusoidal. The CW current frequency varies according to nrref. The CW current frequency is 5 Hz in sub-synchronous and super-synchronous operation, and it is 0 Hz in synchronous operation, which is consistent with Eqs. (8) and (9).
The PW current amplitude varies with Pp and Qp. The CW current amplitude is related to the active and reactive power of PW and the speed. Pp changes to –10 kW and –15 kW at 1.3 s and 2 s respectively, which results in the increase of PW current amplitude at the corresponding time. Qp affects the distribution of PW current and CW current to the excitation current. All excitation current is provided by CW current when Qp = 0 kvar (0–0.9 s and 1.5–3.5 s), and the excitation current is provided by both CW current and PW current when Qp = 5 kvar (0.9–1.5 s). At 0.9 s, Qp changes from 0 kvar to 5 kvar, and PW current provides part of the excitation current. Therefore, the amplitude of PW current increases and the amplitude of CW current decreases at 0.9 s. At 1.5 s, Qp changes from 5 kvar to 0 kvar, and PW current no longer provides the excitation current. All excitation current is provided by CW current, resulting in an increase in the amplitude of CW current and a decrease in the amplitude of PW current.
After the converter switch fails, the fault-tolerant control strategy proposed can make Pp and Qp follow the set value to change rapidly (the transition time occurs within 0.01 s). The PW active power deviation can be kept within ±0.2 kW when the OW-BDFRG is in sub-synchronous stable operation and it can be kept within ±0.5 kW in super-synchronous stable operation. When the OW-BDFRG is in synchronous stable operation state, the active power deviation of PW can be controlled within ±0.1 kW. During this time, the power on the PW side is provided by the mechanical power input from the rotating shaft and the CW side in the DC excitation state. However, the synchronous speed is only a specific speed point and the OW-BDFRG usually operates in a doubly fed state.
The reactive power deviation is stably controlled within ±0.1 kvar throughout the entire operation process when one switch fails, and within ±0.4 kvar when two switches fails. The synthesized voltage vector available is significantly reduced, and the number of sectors is only 6, resulting in a relatively rough control when the following faults occur: Sa1 and Sb3, Sa1 and Sd3, Sa2 and Sb4, Sa2 and Sd4. But the system is still in stable operation. Due to the existence of the hysteresis comparator, the switching frequency is not fixed, thus the maximum switching frequency is 2.5 kHz. Figures 27–29 show the identification results of the sector where the CW flux vector is located. The sector identification result is shown in Fig. 27 when Table 2 is used. The entire plane is evenly subdivided into 18 sectors in this case. The sector value shows a decreasing step state when the generator is in sub-synchronous speed operation, indicating that the CW flux vector rotates clockwise. The sector value shows an increasing step state when the generator is in super-synchronous speed operation, indicating that the CW flux vector rotates counter-clockwise. Figures 28 and 29 show the situation when different switch tables are used. The explanation of Figs. 28 and 29 is similar to the discussion above. The system has a similar performance between post-fault operation and normal operation. The captured results proved that the strategy proposed makes the active and reactive powers track the changes of given values swiftly. Moreover, it makes the system operate stably when power switch fault occurs. The results have illustrated that the fault-tolerant control strategy can simultaneously implement variable-speed constant-frequency operation.
6 Conclusions
For the OW-BDFRG with dual 3LC system, an original fault-tolerant control strategy based on DPC scheme is proposed and investigated, which is the main contribution of this paper. The control strategy has demonstrated a high performance, simple structure, versatility, strong robustness, and good real-time which can improve the fault redundancy capability of the generation system. In addition, the control strategy comprises of a flexible control mode and reduces the converter capacity which is another very important feature of the control strategy proposed. The switching voltage vector selection tables in DPC are constructed under different fault conditions of the dual 3LCs and the system simulation has been verified. The results show that the fault-tolerant control strategy proposed makes the active and reactive powers of the OW-BDFRG track the power given values swiftly and stably. Such occurrence performs well for the fault of one, two, or three power switches and can simultaneously implement variable-speed constant-frequency operation.
Chaal H, Jovanovic M. Toward a generic torque and reactive power controller for doubly fed machines. IEEE Transactions on Power Electronics, 2012, 27(1): 113–121
[2]
Chaal H, Jovanovic M. Practical implementation of sensorless torque and reactive power control of doubly fed machines. IEEE Transactions on Industrial Electronics, 2012, 59(6): 2645–2653
[3]
Cheng M, Zhu Y. The state of the art of wind energy conversion systems and technologies: a review. Energy Conversion and Management, 2014, 88: 332–347
[4]
Attya A B, Ademi S, Jovanović M, Frequency support using doubly fed induction and reluctance wind turbine generators. International Journal of Electrical Power & Energy Systems, 2018, 101: 403–414
[5]
Zhang A, Wang X, Jia W, Indirect stator-quantities control for the brushless doubly fed induction machine. IEEE Transactions on Power Electronics, 2014, 29(3): 1392–1401
[6]
Prasad R, Mulla M. A novel position-sensorless algorithm for field-oriented control of DFIG with reduced current sensors. IEEE Transactions on Sustainable Energy, 2019, 10(3): 1098–1108
[7]
Cheng M, Han P, Buja G, Emerging multiport electrical machines and systems: past developments, current challenges, and future prospects. IEEE Transactions on Industrial Electronics, 2018, 65(7): 5422–5435
[8]
Choi U, Lee J, Blaabjerg F, Open-circuit fault diagnosis and fault-tolerant control for a grid-connected NPC inverter. IEEE Transactions on Power Electronics, 2016, 31(10): 7234–7247
[9]
Yang S, Bryant A, Mawby P, An industry-based survey of reliability in power electronic converters. IEEE Transactions on Industry Applications, 2011, 47(3): 1441–1451
[10]
Lu B, Sharma S. A literature review of IGBT fault diagnostic and protection methods for power inverters. IEEE Transactions on Industry Applications, 2009, 45(5): 1770–1777
[11]
Kwak S. Fault-tolerant structure and modulation strategies with fault detection method for matrix converters. IEEE Transactions on Power Electronics, 2010, 25(5): 1201–1210
[12]
Hoang K D, Zhu Z Q. Comparative performance study of alternate fault-tolerant inverter configurations for direct torque control-based three phase PM BLAC drives under single-phase open-circuit fault. In: 8th IET International Conference on Power Electronics, Machines and Drives (PEMD 2016), Glasgow, UK, 2016
[13]
Welchko B A, Lipo T A, Jahns T M, Fault tolerant three-phase AC motor drive topologies: a comparison of features, cost, and limitations. IEEE Transactions on Power Electronics, 2004, 19(4): 1108–1116
[14]
Shahbazi M, Saadate S, Poure P, Open-circuit switch fault tolerant wind energy conversion system based on six/five-leg reconfigurable converter. Electric Power Systems Research, 2016, 137: 104–112
[15]
Li X, Dusmez S, Akin B, A new active fault-tolerant SVPWM strategy for single-phase faults in three-phase multilevel converters. IEEE Transactions on Industrial Electronics, 2014, 62(6): 3955–3965
[16]
Restrepo J, Berzoy A, Ginart A, Switching strategies for fault tolerant operation of single DC–link dual converters. IEEE Transactions on Power Electronics, 2012, 27(2): 509–518
[17]
Wang Z, Chen J, Cheng M, Fault-tolerant control of paralleled-voltage-source-inverter-fed PMSM drives. IEEE Transactions on Industrial Electronics, 2015, 62(8): 4749–4760
[18]
Chowdhury S, Wheeler P, Patel C, A multilevel converter with a floating bridge for open-end winding motor drive applications. IEEE Transactions on Industry Applications, 2016, 63(9): 5366–5375
[19]
An Q, Liu J, Peng Z, Dual-space vector control of open-end winding permanent magnet synchronous motor drive fed by dual inverter. IEEE Transactions on Power Electronics, 2016, 31(12): 8329–8342
[20]
Jin S, Shi L, Zhu L, Dual two-level converters based on direct power control for an open-winding brushless doubly-fed reluctance generator. IEEE Transactions on Industry Applications, 2017, 53(4): 3898–3906
[21]
Chaal H, Jovanovic M. Power control of brushless doubly-fed reluctance drive and generator systems. Renewable Energy, 2012, 37(1): 419–425
[22]
Zhao W, Wu B, Zhu Q. Fault-tolerant direct thrust force control for a dual inverter fed open-end winding linear vernier permanent-magnet motor using improved SVPWM. IEEE Transactions on Industrial Electronics, 2018, 65(9): 7458–7467
RIGHTS & PERMISSIONS
Higher Education Press
AI Summary 中Eng×
Note: Please be aware that the following content is generated by artificial intelligence. This website is not responsible for any consequences arising from the use of this content.