Comparative analysis of steady-state and dynamic models for grid-connected photovoltaic farm performance monitoring: A case study of Huawei SUN2000-60KTL-M0 inverter
Dias Prihatmoko , Rustam Asnawi , Moh. Khairudin , Nor Azlan Othman
Energy Storage and Conversion ›› 2026, Vol. 4 ›› Issue (3) : 4726
This study evaluates the solar-to-electrical energy conversion performance of a 63.24 kWp grid-connected photovoltaic (PV) farm equipped with a Huawei SUN2000-60KTL-M0 (60 kW) inverter by comparing a steady-state diagnostic model against a dynamic observability assessment. A single-instant snapshot of 12 PV strings on 26 June 2026 identified three non-producing strings (PV6, PV7, PV8), reducing string availability to 75.0% and causing an instantaneous DC power shortfall of approximately 6.0 kW (23.6% of currently achievable capacity). Inverter DC-to-AC conversion efficiency was 98.72% and the observed daily-equivalent capacity factor was 15.48%, both computed directly from measured values. Performance Ratio is reported as not evaluable due to the absence of temporally overlapping plane-of-array irradiance data. The dynamic assessment evaluates day-to-day energy temporal variability and historical hourly weather variability from measured June 2026 and 2020–2025 records (mean absolute daily ramp 12.66%, daily energy CV 19.45%), while sub-minute electrical transient characteristics remain not evaluable owing to the lack of sub-minute electrical logging. A Model Observability Score (MOS) and Data Resolution Adequacy Index (DRAI) are computed from an a priori parameter registry. The steady-state model achieves an MOS of 87.5% (7 of 8 applicable parameters), while the dynamic model achieves 25.0% (4 of 16), with the gap concentrated in the electrical-transient domain and attributable to instrumentation limitations. A phased instrumentation roadmap is proposed. The findings provide a transparent, auditable template for determining appropriate monitoring depth in tropical grid-connected PV operations and maintenance practice.
photovoltaic monitoring / steady-state model / dynamic model / performance ratio / grid-connected PV
| [1] |
|
| [2] |
|
| [3] |
|
| [4] |
IEC. IEC 61724-1:2021, Photovoltaic System Performance-Part 1: Monitoring, 2nd ed. International Electrotechnical Commission; 2021. Available online: https://webstore.iec.ch/en/publication/65561 |
| [5] |
|
| [6] |
|
| [7] |
|
| [8] |
IEEE/IEC 60255-118-1:2018. Measuring Relays and Protection Equipment-Part 118-1: Synchrophasor for Power Systems-Measurements. IEEE/IEC; 2018. Available online: https://standards.ieee.org/ieee/60255-118-1/5724/ |
| [9] |
|
| [10] |
|
| [11] |
|
| [12] |
|
| [13] |
|
| [14] |
|
| [15] |
|
| [16] |
|
| [17] |
|
| [18] |
|
| [19] |
|
| [20] |
|
| [21] |
|
| [22] |
Huawei Technologies Co., Ltd. SUN2000-60KTL-M0 Smart String Inverter-Technical Specifications. Available online: https://solar.huawei.com/-/media/Solar/attachment/pdf/au/datasheet/SUN2000-60KTL-M0.pdf (accessed on 13 July 2026). |
| [23] |
|
| [24] |
|
| [25] |
|
| [26] |
|
/
| 〈 |
|
〉 |