Abstract

Nonstructural components (NSCs) contribute about 80%–90% of the construction investment in a modern public building. The post-earthquake safety and normal operation of NSCs are necessary to achieve performance-based design and resilient buildings. The piping system is one of the most essential nonstructural systems to preserve the post-earthquake functionality of public buildings.To accurately evaluate the seismic performance and vulnerability of piping systems in buildings, a component-level seismic fragility database is urgently to be developed. System composition, failure modes of piping systems, and induced consequences during previous earthquakes are introduced first in this article Then a concise description of component-level fragility methodology suggested by the Applied Technology Council is presented. Seismic fragility database of piping components including pipes, piping joints, and seismic braces through quasistatic tests are developed based on the fragility analysis method. Experimental results from available literature are summarized and presented in the form of seismic fragility curves. Specifc hysteretic curves of these components are also presented, which are used for the calibration of numerical models. In addition the future research directions on the seismic fragility of piping components are summarized and prospected. The developed component-level seismic fragility database can be used to help understand the seismic performance and post-earthquake damage states of the piping system. Seismic performance assessment and seismic fragility analysis of modern piping systems can be conducted using the developed database and numerical simulation method.

Keywords

damage states / numerical model / piping systems / quasi-static tests / seismic fragility curves

Cite this article

Download citation ▾
Qingxue Shang, Zhenyun Tang, Tao Wang. Component-level seismic fragility database of suspended piping systems in buildings. Earthquake Engineering and Resilience, 2024, 3(4): 612-636 DOI:10.1002/eer2.100

登录浏览全文

4963

注册一个新账户 忘记密码

References

[1]

Taghavi S, Miranda E. Response Assessment of Nonstructural Building Elements. PEER Report 2003/05. Pacific Earthquake Engineering Research Center;2003.

[2]

Filiatrault A, Sullivan T. Performance-based seismic design of nonstructural building components: the next frontier of earthquake engineering. Earthquake Engineer Engineer Vibrat. 2014;13(1):17-46.

[3]

Dhakal RP, Pourali A, Tasligedik AS, et al. Seismic performance of non-structural components and contents in buildings: an overview of NZ research. Earthquake Engineer Engineer Vibrat. 2016;15(1):1-17.

[4]

Wang T, Shang Q, Li J. Seismic force demands on acceleration-sensitive nonstructural components: a state-of-the-art review. Earthquake Engineer Engineer Vibrat. 2021;20(1):39-62.

[5]

Shi Y, Wang Y, Zhang M, Ding Y, Li ZX. Seismic performance analysis of steel frame structures with separated three-dimensional isolation. Earthquake Engineer Resil. 2023;2(1):52-73.

[6]

Cornell CA, Krawinkler H. Progress and challenges in seismic performance assessment. PEER Center News. 2000;3(2):1-4.

[7]

FEMA P58. Seismic Performance Assessment of Buildings, Volume 1 and 2 –Methodology. Applied Technology Council (ATC);2012.

[8]

Wang C, Ayyub BM. Time-dependent seismic resilience of aging repairable structures considering multiple damage states. Earthquake Engineer Resil. 2022;1(1):73-87.

[9]

Tian Y, Filiatrault A, Mosqueda G. Experimental seismic fragility of pressurized fire suppression sprinkler piping joints. Earthquake Spectra. 2014;30(4):1733-1748.

[10]

Blasi G, Aiello MA, Maddaloni G, Pecce MR. Seismic response evaluation of medical gas and fire-protection pipelines’Tee-Joints. Engineer Struct. 2018;173:1039-1053.

[11]

Qiu L, Shang Q, Li J, Pan P, Wang T. Numerical simulation and experimental validation of the seismic response of suspended grooved-fit piping systems. Engineer Struct. 2023;293:116615.

[12]

Yu P, Zhai C, Liu J, Pei S, Song Z, Xie L. Resilience assessment methods for hospitals subjected to earthquakes: state of the art. Earthquake Engineer Resil. 2022;1(1):40-59.

[13]

Shang Q, Wang T, Li J. Seismic resilience assessment of emergency departments based on the state tree method. Struct Saf. 2020;85:101944.

[14]

Shang Q, Wang T, Li J. A quantitative framework to evaluate the seismic resilience of hospital systems. J Earthquake Engineer. 2022;26(7):3364-3388.

[15]

Miranda E, Mosqueda G, Retamales R, Pekcan G. Performance of nonstructural components during the 27 February 2010 Chile earthquake. Earthquake Spectra. 2012;28(S1):453-471.

[16]

Filiatrault A, Uang C-M. Folz B, Christopoulos C, Gatto K. Reconnaissance Report of the February 28, 2001 Nisqually (Seattle-Olympia) Earthquake. Structural Systems Research Project Report No. SSRP-2001/02, Department of Structural Engineering. University of California;2001.

[17]

Ju BS. Seismic Fragility of Piping System. Ph.D. Dissertation. North Carolina State University;2011.

[18]

Fleming RP. Analysis of Fire Sprinkler System Performance in the Northridge Earthquake. Report No. NIST-GCR-98-636. U.S. Department of Commerce, Building and Fire Research Laboratory, National Institute of Standards and Technology;1998.

[19]

OSHPD. The Northridge Earthquake: A Report to the Hospital Building Safety Board on the Performance of Hospitals. Office of Statewide Health Planning and Development, Facilities Development Division;1995.

[20]

Ayres JM. and Ezer Associates Inc. Northridge Earthquake Hospital Water Damage Study. Office of Statewide Health Planning and Development;1996.

[21]

Steinbrugge K. Earthquakes, Volcanoes, and Tsunamis: An Anatomy of Hazards. Report of Skandia America Group;1982.

[22]

McKevitt WE, Timler PAM, Lo KK. Nonstructural damage from the Northridge earthquake. Can J Civil Engineer. 1995;22(2):428-437.

[23]

FM Global. Nisqually (Seattle, WA, USA). Earthquake, Understanding the Hazard, Report P0042;2001.

[24]

Dillingham JS, Goel RK. Dynamic Properties of Fire Sprinkler Systems. Department of Civil &Environmental Engineering. California Polytechnic State University;2002.

[25]

LeGrone PD. An analysis of fire sprinkler system failures during the Northridge earthquake and comparison with the seismic design standard for these systems. 13th World Conference on Earthquake Engineering Conference Proceedings, August 1–6, 2004, Vancouver, B.C., Canada.

[26]

Chock G. Preliminary observations on the Hawai’i earthquakes of October 15. EERI Special Earthquake Report;2006.

[27]

Antaki G, Guzy D. Seismic Testing of Grooved and Threaded Fire Protection Joints and Correlation with NFPA Seismic Design Provisions. ASME 1998, PVP. 364. Seismic Engineering-1998;1998:69-75.

[28]

He SW, Qu Z, Ye LH. Experiment study on the seismic fragility of water supply pipelines in buildings [in Chinese]. China Civil Engineer J. 2018;51(10):11-19.

[29]

Wang T, Shang Q, Chen X, Li J. Experiments and fragility analyses of piping systems connected by grooved fit joints with large deformability. Front Built Environ. 2019;5:49.

[30]

Malhotra PK, Senseny PE, Braga AC, Allard RL. Testing sprinkler-pipe seismic-brace components. Earthquake Spectra. 2003;19(1):87-109.

[31]

Wood RL, Hutchinson TC, Hoehler MS, Kreidl B. Experimental characterization of trapeze assemblies supporting suspended non-structural systems. Proceedings of the 10th U.S. National Conference on Earthquake Engineering, Paper No. 905, Anchorage, Alaska;2014.

[32]

Filiatrault A, Perrone D, Brunesi E, Beiter C, Piccinin R. Effect of cyclic loading protocols on the experimental seismic performance evaluation of suspended piping restraint installations. Int J Pressure Vessels Piping. 2018;166:61-71.

[33]

Perrone D, Filiatrault A, Peloso S, Brunesi E, Beiter C, Piccinin R. Experimental seismic response evaluation of suspended piping restraint installations. Bullet Earthquake Engineer. 2020;18:1499-1524.

[34]

Shang QX. Seismic Performance Study and Fragility Analysis of Pipeline System. Master Dissertation, Institute of Engineering Mechanics, China. Earthquake Administration;2018 [in Chinese].

[35]

Shang QX, Li Z, Liu RK, Wang T. Experimental study of properties of aseismic braces used in pipeline systems (in Chinese). Engineer Mechan. 2018;35(S1):120-125, 133.

[36]

Porter K, Kennedy R, Bachman R. Creating fragility functions for performance based earthquake engineering. Earthquake Spectra. 2007;23(2):471-489.

[37]

National Earthquake Hazards Reduction Program (NEHRP). “Prestandard and commentary for the seismic rehabilitation of buildings,”. FEMA 356, Federal Emergency Management Agency (FEMA);2000.

[38]

Multi-hazard loss estimation methodology, earthquake model National Earthquake Hazards Reduction Program (NEHRP). HAZUS-MH MR3 technical manual;2003.

[39]

FEMA 461. Interim protocols for determining seismic performance characteristics of structural and nonstructural components through laboratory testing. Federal Emergency Management Agency;2007.

[40]

Matsubara Y, Kojima K, Zhang Z, Kanao I, Kurata M. Cyclic bending tests on several diameters carbon steel pipe for ordinary piping. J Struct Engineer B. 2023;69:345-351.

[41]

Approval Standard for Seismic Sway Braces for Pipe, Tubing and Conduit. Class Number 1950. FM Approvals LLC;2013.

[42]

Shang Q, Qiu L, Wang T, Li J. Experimental and analytical study on performance of seismic sway braces for suspended piping systems. J Build Engineer. 2022;57:104826.

[43]

Yue F, Jaisee S, Zhu B, Ooi YH. Experimental study on friction seismic sway bracings for seismic protection of building nonstructural components. J Earthquake Engineer. 2022;26:7297-7318.

[44]

Liu R, Jiang T, Dai J, Yang Y, Bai W. Experimental study on the seismic performance of seismic bracing in important buildings. Sustainability. 2023;15:9523.

[45]

Soroushian S, Zaghi AE, Maragakis M, Echevarria A, Tian Y, Filiatrault A. Analytical seismic fragility analyses of fire sprinkler piping systems with threaded joints. Earthquake Spectra. 2015;31(2):1125-1155.

[46]

Soroushian S, Zaghi AE, Maragakis E, Echevarria A, Tian Y, Filiatrault A. Seismic fragility study of fire sprinkler piping systems with grooved fit joints. J Structural Engineering. 2015;141(6):04014157.

RIGHTS & PERMISSIONS

2024 Tianjlin University and John Wiley & Sons Australia, Ltd.