Energy performance assessment on central air-conditioning system of commercial building: A case study in China

Xuan Zhou , Si-zhen Lian , Jun-wei Yan , Ying-zi Kang

Journal of Central South University ›› 2015, Vol. 22 ›› Issue (8) : 3168 -3179.

PDF
Journal of Central South University ›› 2015, Vol. 22 ›› Issue (8) : 3168 -3179. DOI: 10.1007/s11771-015-2854-6
Article

Energy performance assessment on central air-conditioning system of commercial building: A case study in China

Author information +
History +
PDF

Abstract

Energy performance assessment on central air-conditioning system is essential to optimize operating, reduce operating costs, improve indoor environmental quality, and determine whether the retrofitting of the equipment is necessary. But it is difficult to evaluate it reasonably and comprehensively due to its complexity. A “holistic” approach was discussed to evaluate the energy performance of central air-conditioning system for an extra-large commercial building in a subtropical city. All procedures were described in detail, including field investigation method, field measurement instruments, data processing and data analyzing. The main factors affecting energy consumption of air-conditioning system were analyzed and the annual cooling-energy use intensity of this building was calculated and also compared with other shopping malls and other types of buildings in Guangzhou. And COP (coefficient of performance) of chiller, water transfer factor of chilled water system and cooling water system were taken into consideration. At last, the thermal comfort and indoor air quality issues were addressed. The results show that the chilled water pumps are over-sized and the indoor environmental quality should be improved. The purpose of this work is to provide reference for energy performance assessment method for air-conditioning system.

Keywords

energy performance assessment / thermal comfort / indoor air quality / central air-conditioning system / energy saving

Cite this article

Download citation ▾
Xuan Zhou, Si-zhen Lian, Jun-wei Yan, Ying-zi Kang. Energy performance assessment on central air-conditioning system of commercial building: A case study in China. Journal of Central South University, 2015, 22(8): 3168-3179 DOI:10.1007/s11771-015-2854-6

登录浏览全文

4963

注册一个新账户 忘记密码

References

[1]

de SANTOLIL, FraticelliF, FornariF, CaliceC. Energy performance assessment and a retrofit strategies in public school buildings in Rome[J]. Energy and Buildings, 2014, 68(1): 196-202

[2]

QuangT N, HeC-r, KnibbsL D, DearR D. Cooptimisation of indoor environmental quality and energy consumption within urban office buildings [J]. Energy and Buildings, 2014, 85(12): 225-234

[3]

HansenM, RasulMPerformance assessment and improvement of an existing air conditioning system of a supermarket: A case study on Bi-Lo supermarket [C], 2008CambridgeUniversity of Cambridge55-60

[4]

FunamiK, NishiHEvaluation of power consumption and comfort using inverter control of air-conditioning [C], 20113236-3241

[5]

ZhangD-l, ZhangX, CaiNing. Study on energy saving possibility of digital variable multiple air conditioning system in three office buildings in Shanghai [J]. Energy and Buildings, 2014, 75(6): 23-28

[6]

YangW-huitStudy on comprehensive energy-saving operation model of public buildings air-conditioning system [D], 2008ChongqingCollege of Power Engineering, Chongqing University

[7]

FanY-q, HayashiT, ItoK. Coupled simulation of BES-CFD and performance assessment of energy recovery ventilation system for office model [J]. Journal of Central South University, 2012, 19(3): 633-638

[8]

YangC-z, WuX-y, LiW-jing. Energy consumption status and energy saving potentials of air conditioning systems in public buildings of Changsha [J]. HV & AC, 2005, 35(12): 39-43

[9]

ZhouX-q, LiuF, ChenW-q, YangS-r, DingY-fei. Investigation and study on energy consumption of public buildings in Guangzhou [J]. Building Science, 2007, 23(12): 76-80

[10]

DBJ 15-51—2007. Design standard for energy efficiency of public buildings[S].

[11]

GB/T 17981 — 2007. Economic Operation of Air Conditioning Systems [S]. (in Chinese)

[12]

GB 50019—2003. Code for Design of heating, ventilation and air-conditioning [S]. (in Chinese)

[13]

GB/T 18204.13—2003, Methods for determination of air temperature in public places [S]. (in Chinese)

[14]

ISO International Standard 7730—2005, Third edition. Ergonomics of the thermal environment — Analytical determination [S].

[15]

KongkiatumpaiPStudy of impact of indoor set point temperature on energy consumption of air-conditioner and green-house gases emission [R], 1999ThailandSchool of Energy Technology Program, King Mongkut’s University of Technology Thonburi