Power swing and voltage collapse identification schemes for correct distance relay operation in power system
Ahmad F. Abidin , Azah Mohamed , Hussain Shareef
Journal of Central South University ›› 2013, Vol. 20 ›› Issue (4) : 988 -1000.
The new techniques were presented for preventing undesirable distance relay maloperation during voltage collapse and power swings in transmission grids. Initially, the work focused on the development of a fast detection of voltage collapse and a three-phase fault at transmission lines by using under impedance fault detector (UIFD) and support vector machine (SVM). Likewise, an intelligent approach was developed to discriminate a fault, stable swing and unstable swing, for correct distance relay operation by using the S-transform and the probabilistic neural network (PNN). To illustrate the effectiveness of the proposed techniques, simulations were carried out on the IEEE 39-bus test system using the PSS/E and MATLAB software.
under impedance fault detector / distance relay / fault / voltage collapse