An active pipe-embedded building envelope for utilizing low-grade energy sources

Jun-long Xie , Qiu-yuan Zhu , Xin-hua Xu

Journal of Central South University ›› 2012, Vol. 19 ›› Issue (6) : 1663 -1667.

PDF
Journal of Central South University ›› 2012, Vol. 19 ›› Issue (6) : 1663 -1667. DOI: 10.1007/s11771-012-1190-3
Article

An active pipe-embedded building envelope for utilizing low-grade energy sources

Author information +
History +
PDF

Abstract

An active pipe-embedded building envelope, which is an external wall or roof with pipes embedded inside, was presented. This structure may utilize the circulating water in the pipe to transfer heat or coolth inside directly. This kind of structure is named “active pipe-embedded building envelope” due to dealing with the thermal energy actively inside the structure mass by circulating water. This structure not only deals with thermal energy before the external disturbance becomes cooling/heating load by using the circulating water, but also may use low-grade energy sources such as evaporative cooling, solar energy, and geothermal energy. In the meantime, this structure can also improve the indoor thermal comfort by tempering the internal wall surface temperature variation due to the thermal removal in the mass. This work further presents the thermal performance of this structure under a typical hot summer weather condition by comparing it with that of the conventional external wall/roof with numerical simulation. The results show that this pipe-embedded structure may reduce the external heat transfer significantly and reduce the internal wall surface temperature for improving thermal comfort. This work also presents the effects of the water temperature and the pipe spacing on the heat transfer of this structure. The internal surface heat transfer may reduce by about 2.6 W/m2 when the water temperature reduces by 1 °C as far as a brick wall with pipes embedded inside is concerned. When the pipe spacing reduces by 50 mm, the internal wall surface heat flux can also reduce by about 2.3 W/m2.

Keywords

active pipe-embedded building envelope / thermal performance / thermal comfort / simulation analysis / low-grade energy source / pipe spacing

Cite this article

Download citation ▾
Jun-long Xie, Qiu-yuan Zhu, Xin-hua Xu. An active pipe-embedded building envelope for utilizing low-grade energy sources. Journal of Central South University, 2012, 19(6): 1663-1667 DOI:10.1007/s11771-012-1190-3

登录浏览全文

4963

注册一个新账户 忘记密码

References

[1]

SnijdersA. L.. Aquifer seasonal cold storage for space conditioning: Some cost-effective applications [J]. ASHRAE Transactions, 1992, 98(1): 1015-022

[2]

MeierhansR. A.. Slab cooling and earth coupling [J]. ASHRAE Transactions, 1993, 99(2): 511-518

[3]

MeierhansR. A.. Room air conditioning by means of overnight cooling of the concrete ceiling [J]. ASHRAE Transactions, 1996, 102(1): 693-697

[4]

XuX.-h., ZhouL.-j., ZhuQ.-yuan.. Technologies and applications of pipe-embedded building structures for air-conditioning system [J]. Building Science, 2009, 125(10): 105-109

[5]

XuX.-h., WangS.-w., WangJ.-b., XiaoFu.. Active pipe-embedded structures in buildings for utilizing low-grade energy sources: A review [J]. Energy and Buildings, 2010, 42(10): 1567-1581

[6]

LehmannB., DorerV., KoschenzM.. Application range of thermally activated building systems tabs [J]. Energy and Buildings, 2007, 39(5): 593-598

[7]

KennettS.. Surface treatment [J]. Building Services Journal, 2006, 28(12): 39-41

[8]

FloridesG., KalogirouS.. Ground heat exchangers-A review of systems, models and applications [J]. Renewable Energy, 2007, 32(15): 2461-2478

[9]

LiuX. B., ReesS. J., SpitlerJ. D.. Modeling snow melting on heated pavement surfaces: Part I. Model development [J]. Applied Thermal Engineering, 2007, 27(5/6): 1115-1124

[10]

StephensonD. G., MitalasG. P.. Cooling load calculations by thermal response factors [J]. ASHRAE Transactions, 1967, 73: III1.1-III1.7

[11]

WangS.-w., ChenY. M.. A simple procedure for calculating thermal response factors and conduction transfer functions of multilayer walls [J]. Applied Thermal Engineering, 2002, 22: 333-338

[12]

TangZ.-w., JinN., YanG.-lan.. Numerical study on unsteady heat transfer of underground heat exchanger of GCHP [J]. Renewable Energy, 2008, 26(1): 55-58

[13]

LiuJ., ZhangX., GaoJ., LiK.-shan.. Research of soil temperature restoration characteristics of ground-source heat pump systems [J]. Heating Ventilating & Air Conditioning, 2008, 38(11): 147-150

[14]

OppeltT., RiehlI., GrossU.. Modelling of the borehole filling of double U-pipe heat exchangers [J]. Geothermics, 2010, 39(3): 270-276

[15]

WuY.-p., GanG.-h., VerhoefA.. Experimental measurement and numerical simulation of horizontal-coupled slinky ground source heat exchangers [J]. Applied Thermal Engineering, 2010, 30(16): 2574-2583

[16]

LiN., YuanD.-l., WangY.-h., DiY.-qiang.. Simulation and analysis of cool storage capability of radiant concrete ceilings [J]. Heating Ventilating & Air Conditioning, 2009, 39(7): 143-145