Heat resistance and water protection effectiveness for large single-pane fireproof glass

Quan Shao , Fang Li , Tao Chen , Zhan-hui Sun

Journal of Central South University ›› 2011, Vol. 18 ›› Issue (6) : 2185 -2191.

PDF
Journal of Central South University ›› 2011, Vol. 18 ›› Issue (6) :2185 -2191. DOI: 10.1007/s11771-011-0961-6
Article

Heat resistance and water protection effectiveness for large single-pane fireproof glass

Author information +
History +
PDF

Abstract

The effects and heat transfer mode of water film and sprinkler system on the heat-resistant property associated with the insulation of a fireproof glass were investigated. In the experiments, fireproof glass with a size of 3 300 mm (height) × 2 200 mm (width) × 12 mm (thickness) was exposed to an oil pool fire with a power of approximately 1.4 MW. The experimental results show that the application of the water film or sprinkler system on the glass can effectively resist the intensive heat from the fire in the test due to the absorption of latent heat. The permitted period of integrity and insulation with a water film and a sprinkler system could be extended to 60 min. It should be noted that the temperature of the glass surface can be kept under 60 °C in a 60 min test. The experimental results suggest that it is feasible to substitute fireproof glass with water film for a fireproof door as long as the water film or sprinkler system can work stably and water can cover the whole surface of the fireproof glass.

Keywords

water film / sprinkler system / heat-resistance / fireproof glass / fire test

Cite this article

Download citation ▾
Quan Shao, Fang Li, Tao Chen, Zhan-hui Sun. Heat resistance and water protection effectiveness for large single-pane fireproof glass. Journal of Central South University, 2011, 18(6): 2185-2191 DOI:10.1007/s11771-011-0961-6

登录浏览全文

4963

注册一个新账户 忘记密码

References

[1]

GB 50045-95.Code for fire protection design of tall buildings [S], 2005, Beijing, China Planning Press

[2]

ThomasW. C., SunderlandJ. E.. Heat transfer between a plane surface and air containing suspended water droplet [J]. Ind Eng Chem Fundam, 1970, 9(3): 369-374

[3]

AiharaT., TagaM., HaraguchiT.. Heat transfer from a uniform heat flux wedge in air-water mist flows [J]. Int J Heat Mass Transfer, 1979, 22: 51-60

[4]

YanW. M., SongC. Y.. Numerical study of liquid film cooling in a turbulent gas stream [J]. Int J Heat Mass Transfer, 1993, 36: 3877-3886

[5]

YanW. M.. Convective heat and mass transfer from a falling film to a laminar gas stream [J]. Warme-und Stoffubertragung, 1993, 29: 79-87

[6]

WuC. W., LinT. H., LeiM. Y., ChungT. H., HuangC. C., ChiangW. T.. Fire test on a non-heat-resistant fireproof glass with down-flowing water film [J]. Fire Safety Science, 2005, 8: 327-338

[7]

WuC. W., LinT. H., LeiM. Y., ChungT. H., HuangC. C., ChiangW. T. W. T.. Fire resistance characteristics of a glass plane with down-flowing water film [J]. Journal of the Chinese Institute of Engineers, 2008, 31(5): 737-744

[8]

WuC. W., LinT. H.. Full-scale evaluations on heat resistance of glass panes incorporated with water film or sprinkler in a room fire [J]. Building and Environment, 2007, 42: 3277-3284

[9]

RichardsonJ. K., OleszkiewiczI.. Fire tests on window assemblies protected by automatic sprinklers [J]. Fire Technology, 1987, 23(2): 115-132

[10]

BeasonD.. Fire endurance of sprinklered glass walls [J]. Fire Journal, 1986, 7: 43-45

[11]

KimA., TaberB., LougheedG.. Sprinkler protection of exterior glazing [J]. Fire Technology, 1998, 34(2): 116-138

[12]

KimA., LougheedG.. Fire protection of windows using sprinklers [J]. Construction Technology Update, 1997, 12: 4-10

[13]

KimA., LougheedG.. The Protection of glazing systems with dedicated sprinklers [J]. Journal of Fire Protection Engineering, 1990, 2(2): 49-59

[14]

NiZ.-chu.Experimental study on sprinkler protection of single-pane fire-resistant glass [D], 2005, Hefei, University of Science and Technology of China

[15]

ShuX.-ming.. Experimental study of single-pane fire-resistant glass performance with sprinkler protection [J]. Engineering Science, 2006, 8(6): 64-68

AI Summary AI Mindmap
PDF

124

Accesses

0

Citation

Detail

Sections
Recommended

AI思维导图

/