Operating performance of novel reverse-cycle defrosting method based on thermal energy storage for air source heat pump

Jian-kai Dong , Yi-qiang Jiang , Yang Yao , Xue-dan Zhang

Journal of Central South University ›› 2011, Vol. 18 ›› Issue (6) : 2163 -2169.

PDF
Journal of Central South University ›› 2011, Vol. 18 ›› Issue (6) : 2163 -2169. DOI: 10.1007/s11771-011-0958-1
Article

Operating performance of novel reverse-cycle defrosting method based on thermal energy storage for air source heat pump

Author information +
History +
PDF

Abstract

To solve the fundamental problem of insufficient heat available during defrosting while ensuring the efficient and safe system operation for air-source heat pumps (ASHPs). A novel reverse-cycle defrosting (NRCD) method based on thermal energy storage to eliminate frost off the outdoor coil surface was developed. Comparative experiments using both the stand reverse cycle defrosting (SRCD) method and the NRCD method were carried out on an experimental ASHP unit with a nominal 2.5 kW heating capacity. The results indicate that during defrosting operation, using the NRCD method improves discharge and suction pressures by 0.24 MPa and 0.19 MPa, respectively, shortens defrosting duration by 60%, and reduces the defrosting energy consumption by 48.1% in the experimental environment, compared with those by the use of SRCD method. Therefore, using the NRCD method can shorten the defrosting duration, improve the indoor thermal comfort, and reduce the defrosting energy consumption in defrosting.

Keywords

air source heat pump / thermal energy storage / phase change material / reverse-cycle defrosting

Cite this article

Download citation ▾
Jian-kai Dong, Yi-qiang Jiang, Yang Yao, Xue-dan Zhang. Operating performance of novel reverse-cycle defrosting method based on thermal energy storage for air source heat pump. Journal of Central South University, 2011, 18(6): 2163-2169 DOI:10.1007/s11771-011-0958-1

登录浏览全文

4963

注册一个新账户 忘记密码

References

[1]

ByunJ. S., LeeJ., JeonC. D.. Frost retardation of an air-source heat pump by the hot gas bypass method [J]. International Journal of Refrigeration, 2002, 25: 405-413

[2]

KondepudiS. N., O’NealD. L.. Effect of different fin configuration on the performance of finned-tube heat exchanger under frosting conditions [J]. ASHRAE Transactions, 1990, 96(2): 439-444

[3]

KondepudiS. N., O’NealD. L.. Frosting performance of tube fin heat exchanger with wavy and corrugated fins [J]. Experimental Thermal and Fluid Science, 1991, 4: 613-618

[4]

O’NealD. L., PetersonK. T., AnandN. K., SchliesingJ. S.. Refrigeration system dynamics during the reversing cycle defrosting [J]. ASHRAE Transaction, 1989, 95: 689-698

[5]

PayneV., O’NealD. L.. Defrost cycle performance for an air-source heat pump with a scroll and a reciprocating compressor [J]. International Journal of Refrigeration, 1995, 18: 107-112

[6]

HuangD., LiQ.-x., YuanX. L.. Comparison between hot-gas bypass defrosting and reverse-cycle defrosting methods on an air-to-water heat pump [J]. Applied Energy, 2009, 86: 1697-1703

[7]

ChoH. Y., KimaY. C., JangI. K.. Performance of a showcase refrigeration system with multi-evaporator during on-off cycling and hot-gas bypass defrost [J]. Energy, 2005, 30: 1915-1930

[8]

ByunJ. S., LeebJ. H., JeonC. D.. Frost retardation of an air-source heat pump by the hot gas bypass method [J]. International Journal of Refrigeration, 2008, 31: 328-334

[9]

HewittN., HuangM. J.. Defrost cycle performance for a circular shape evaporator air source heat pump [J]. International Journal of Refrigeration, 2008, 31: 444-452

[10]

HuangD., YuanX.-l., ZhangX.-qun.. Effects of fan-starting methods on the reverse-cycle defrost performance of an air-to-water heat pump [J]. International Journal of Refrigeration, 2004, 27: 869-875

[11]

JheeS., LeeK. S., KimW. S.. Effect of surface treatments on the frosting/defrosting behavior of a fin-tube heat exchanger [J]. International Journal of Refrigeration, 2002, 25: 1047-1053

[12]

WangS. W., LiuZ. Y.. A new method for preventing HP from frosting [J]. Renewable Energy, 2005, 30: 753-761

[13]

KinsaraA. A., ElsayedM. M., OmarM. R.. Proposed energy-efficient air-conditioning system using liquid desiccouldt [J]. Applied Thermal Engineering, 1996, 16: 791-806

[14]

JainS., BansalP. K.. Performance analysis of liquid desiccouldt dehumidification systems [J]. International Journal of Refrigeration, 2007, 30: 861-872

[15]

ChenY.-g., GuoX.-min.. Dynamic defrosting characteristics of air source heat pump and effects of outdoor air parameters on defrost cycle performance [J]. Applied Thermal Engineering, 2009, 29: 2701-2707

[16]

WattersR. J., O’NealD. L., DennisL.. Effect of fin staging on frost/defrost performance of a two-row heat pump evaporator at standard test conditions [J]. ASHRAE Transactions, 2001, 107: 240-249

[17]

MeiV. C., DomitrovicR. E., ChenF. C., KilpatrickJ. K.. A frost-less heat pump [J]. ASHRAE Transactions, 2002, 5: 452-459

[18]

XuY. L., LiuD.. Preliminary super cooling research on calcium chloride hexahydrate as phase change material [J]. Material Engineering, 2006, Z1: 218-221