Features of the design of ventilation and air conditioning in the buildings of medical institutions (HCI)*
Redaktsionnaya kollegiya
Refrigeration Technology ›› 2004, Vol. 93 ›› Issue (9) : 42 -44.
Features of the design of ventilation and air conditioning in the buildings of medical institutions (HCI)*
The calculated air temperatures in the serviced area of the premises are determined depending on their purpose in accordance with tables 9 and 10, both for the cold and for the warm period of the year. In the operating room, the air temperature is not more than 22 °C. The relatively low temperature is explained by the increase in the concentration of bacteria during operations and the deterioration in the heat transfer of personnel due to the use of rubber gloves and masks with increasing temperature.