New Algorithm for Fault Superimposed Quantities Based on Superimposed Network
BI Jian-guang, DONG Xin-zhou, GUO Yong-ji
Author information+
Department of Electrical Engineering, Tsinghua University, Beijing 100084, China;
Show less
History+
Published
05 Mar 2006
Issue Date
05 Mar 2006
Abstract
A new algorithm for fault superimposed quantity (FSIQ) is presented and analyzed. The network equations are built up by combining fault superimposed networks (FSIN) with the boundary conditions of FSIQ at the fault point and are solved with the Newton iterative method. The algorithm has clear physical meaning and does not require an intermediate procedure to derive FSIQ. The algorithm is implemented by computer programming, and the results of calculations show that the algorithm is fast and accurate. The method can be used not only to calculate FSIQ in the complex power systems with simple or multiple faults, but also to analyze and evaluate the performance of the protective relays and automatic devices based on FSIQ.
BI Jian-guang, DONG Xin-zhou, GUO Yong-ji.
New Algorithm for Fault Superimposed Quantities Based on Superimposed Network. Front. Electr. Electron. Eng., 2006, 1(1): 58‒62 https://doi.org/10.1007/s11460-005-0001-0